Taekhee Lee, Teresa L Barone, David S Yantek, Lee Portnoff, Yi Zheng
Journal: Journal of occupational and environmental hygiene 2023;20(7):289-303
PMID: 37084391
The objective of this study is to evaluate a prototype local ventilation system (LVS) intended to reduce retail store workers' exposure to aerosols. The evaluation was carried out in a large aerosol test chamber where relatively uniform concentrations of polydisperse sodium chloride and glass-sphere particles were generated to test the system with nano- and micro-size particles. In addition, a cough simulator was constructed to mimic aerosols released by mouth breathing and coughing. Particle reduction efficiencies of the LVS were determined in four different experimental conditions using direct reading instruments and inhalable samplers. The particle reduction efficiency (%) depended on the position beneath the LVS, but the percentage was consistently high at the LVS center as follows: (1) > 98% particle reduction relative to background aerosols; (2) > 97% in the manikin's breathing zone relative to background aerosols; (3) > 97% during mouth breathing and coughing simulation; and (4) > 97% with a plexiglass barrier installation. Lower particle reduction (<70%) was observed when the LVS airflow was disturbed by background ventilation airflow. The lowest particle reduction (<20%) was observed when the manikin was closest to the simulator during coughing.